When using a gas boiler, it is found that there is a problem with the burner. How to solve it
2020.9.29

If you find that there is a problem with the burner while using the gas boiler, how can you troubleshoot and solve it? Let's take a look with Henan Taiguo boiler brand! The "Silver City" brand products currently produced by Taiguo Boiler include oil (gas), coal-fired, electric steam, hot water boilers, organic heat carrier heating furnaces, high and medium temperature hot blast stoves, second-class pressure vessels and non-standard products There are 23 series and more than 150 specifications and models. The "Yincheng" brand boiler products have superior quality and performance, ranking high in the country, and have won the national, ministerial and provincial "high-quality and energy-saving products" awards.


1. The ignition rod of the gas boiler burner does not ignite

The possible reasons are: carbon slag and oil stain in the gap of the ignition rod; the ignition rod is broken. Wet. Leakage; the distance between the ignition rods is incorrect, too long or short; the insulation of the ignition rod is damaged and short-circuited to the ground; the ignition cable and the transformer are faulty: the cable is disconnected, the connector is damaged and causes a short circuit during ignition; the transformer is disconnected or appears Other failures.

Treatment measures include: clear, replace, adjust the distance, replace the line, and replace the transformer.


2. The ignition rod of the gas boiler has sparks but does not ignite

The reasons may be: the ventilation gap of the cyclone is blocked by carbon deposits, and the ventilation is poor; the oil nozzle is dirty, blocked or worn; the setting angle of the air damper is too small; the distance between the tip of the ignition rod and the leading edge of the oil nozzle is inappropriate (too protruding or retracting) ; The solenoid valve of the first oil gun is blocked by debris (small fire oil gun); the oil is too viscous to flow easily or the filter system is blocked or the oil valve is not opened, which makes the oil pump insufficient and low oil pressure; the filter screen of the oil pump is blocked; There is more water (abnormal sound of boiling in the heater).

Treatment measures include: clear; clean first, if not possible, replace with a new one; reduce the test; adjust the distance (3~4mm is better); remove and clean (clean the parts with diesel); check the pipeline, oil filter, and heat preservation equipment ; Remove the peripheral screws of the oil pump, carefully remove the outer cover and take out the oil net inside, soak it with diesel oil; change the oil and try it.


3. When the small fire of the gas boiler is normal, but it turns to the big one, it goes out or flickers unstable

The reasons may be: the air volume of the air damper of the big fire is too high; the micro switch of the oil valve of the big fire (the outermost group of the air door) is not properly set (the air volume of the damper is set larger than that of the big fire); the oil viscosity is too high It is not easy to atomize (heavy oil); the distance between the cyclone and the fuel nozzle is improper; the fuel nozzle is worn or dirty in large fire; the heating temperature of the reserve fuel tank is too high, which causes the steam to make the fuel pumping irregular; the oil in the fuel boiler contains water.

Treatment measures include: gradually reduce the test; increase the heating temperature; adjust the distance (between 0~10mm); clean or replace; set about 50℃; change the oil or drain.

      

4. Increased noise of gas boiler burners

The reasons may be: the shut-off valve in the oil circuit is closed or the oil inlet is insufficient, the oil filter is blocked; the oil inlet temperature is low, the viscosity is too high, or the pump oil inlet temperature is too high; the oil pump is malfunctioning; the fan motor bearing is damaged; the fan impeller is too dirty .

The treatment methods are: check whether the valve in the oil pipeline is open, whether the oil filter is working properly, clean the filter screen of the pump itself; increase or decrease the oil temperature; replace the oil pump; replace the motor or bearing; clean the fan impeller.


Henan Taiguo Boiler Manufacturing Co., Ltd. Zhengzhou Branch and Shanghai Industrial Boiler Research Institute jointly developed a new generation of new coal-fired steam and hot water boiler hot water units integrating heating and bathing. This series of products have the characteristics of novel design, compact structure, large heating area and high thermal efficiency. This series of boilers also have the characteristics of small footprint, energy saving and good environmental protection. Since its listing, it has been favored by a large number of government agencies, hotels and restaurants.


Product Line

more+     

Gas & Oil Fired Boiler
Learn more+ Contact us
Biomass Fired Boiler
Learn more+ Contact us
Coal Fired Boiler
Learn more+ Contact us
Thermal Oil Boiler
Learn more+ Contact us
Electric Heating Boiler
Learn more+ Contact us
Contact Us
* Tel:
* Product:
* Email:
* Name:
*