Equipment maintenance system
1. In order to ensure the safe operation of boilers and prolong their service life, it is necessary to insist on daily maintenance, maintenance and overhaul of boilers, pipes and auxiliary equipment.
2. The boiler water supply system, check valve and balance valve shall be checked and cleaned once a month, and the drainage device shall be cleaned once every two months. The pressure gauge shall be checked and cleaned and flushed, and the pressure gauge and temperature gauge shall be checked every day.
Three, found that the boiler manhole, hand hole, observation hole leakage, leakage, should be tightened in time, seriously damaged should be replaced in time, the boiler water temperature should be reduced to about 60℃.
Four. The safety valve must be manually lifted once a month. When it is found that it is not tight, it should be lifted, lifted and released more quickly.
Five, every day should check whether the water pump leakage, all valves are running, dripping, leakage phenomenon, found the problem should be solved in time.
Six, keep the boiler body clean, no dirt, no leakage, no rust and external corrosion, carefully fill in the equipment maintenance records.
For all inquiries, please fill in the form below (* are required) to send us a brief message, and we will get back to you as soon as possible.